Normally a clarifier runs at one torque value for 90 to 98 percent of the time. This torque value could be termed the "running torque" of the clarifier. Sometimes the running torque is called the "design torque". The drive unit should be designed for this running torque, which will give the most economical mechanism based on the intended use of the clarifier.
The drive unit should be protected from excessive loads that would require it to run
above its design requirements. An alarm should be set that provides adequate
protection, and tells the operator that there is something affecting the
clarifier mechanism. This alarm setting should be above the running torque; 120%
of the running torque is generally sufficient.
Use of an
alarm torque value is beneficial not only in protecting the drive unit, but
also in giving an added range of running torque in case the loading values were
incorrectly selected. The drive unit
should not be designed to run continuously at or near the alarm setting. This
would defeat the reasoning behind choosing the running torque requirement.
For the
protection of the drive unit, a shut-off or cut-off torque rating should be
used. If there is some abnormality in the clarifier causing a rapid increase in
torque, the unit would shut itself off without adversely affecting the
mechanism. Shut-off torque should be
used only as a protective rating, however, and the unit should not be running
continuously at this value; 140% of the running torque appears to be adequate.
If the drive was sized and designed to run continuously at this value, it would
be over-sized and therefore an uneconomical choice consideration.
Peak torque
is the value determined by the supplier of the drive unit indicating what the
unit can handle at a momentary or instantaneous load. This ultimate load should
be of very short duration, e.g. in the three (3) second range, in case the
torque is increased so rapidly that response time to the shut-off mode is not
enough. Peak torque is normally two (2) times the running torque.
As described
above, an overload device is essential for the drive unit so that the alarm and
shut-off torques can be sensed and the unit protected. This is particularly
important in the larger units because a good deal of money is invested in the drive
and adequate protection is critical. Overload protections can be electronic and/or
mechanical. On the smaller drive units, such as those that rest on the bridges
of small clarifiers, the complete range of protection is not as critical. A
simple shear pin device that turns the unit off when an excessive torque is
sensed is generally adequate.
As engineers
and designers progress in their determination of the drive units to be furnished,
they should remember that reputable equipment suppliers stand behind their
drives. It is apparent by the operation of the clarifier if the drive is
working properly. However, if project
engineers state a torque value above the necessary range, they want to be assured
of the results. Therefore, the specification should clearly state desired
torque ratings: running, alarm, and shut-off.
As an
additional requirement for a project, a torque testing procedure could be
specified if required. This is a costly
procedure for most projects, but if the engineer feels he or she is not getting, or
will not get the drive that was specified, he or she could call for torque testing of the
drive unit in the field.
Monday, June 18, 2012
Subscribe to:
Posts (Atom)